Motion Sensor
Motion Sensors are RF devices, thus require the installation of an INSTEON RF
receiver (such as an INSTEON AccessPoint).
The Motion Sensor cannot be linked using Auto Discover. To link a Motion Sensor to
the ISY, please choose the LINK MANAGEMENT pulldown, then NEW INSTEON
DEVICE. Enter the device address manually (found inside the battery compartment),
then select the “2420M INSTEON Motion Sensor” from the Device Type list.
Since the Motion Sensor is a battery-saving RF device, you must put the device into
linking mode to add it to the ISY (and make any changes to the device, such as
adding/removing from scenes). Please follow the on-screen instructions to put the
Motion Sensor into linking mode when prompted (hold SET button for 5 seconds).
Once added to the ISY, the Motion Sensor will show up as 3 nodes. The primary node
is the motion sensing portion of the device, which updates according to sensed motion
(or lack of motion).
There is also a DUSK/DAWN node that will show ON when the device senses darkness
and show OFF when the device senses light. The Motion Sensor will not update this
node until approximately 3.5 minutes after a state change has persisted.
Finally, a Low Battery node will show as ON when the Motion Sensor senses a low
battery condition and notifies the ISY.
Motion Sensors support several unique options, such as:
Timeout (minutes) - Defines the period of inactivity before the Motion Sensor will
send an Off. Default = 1 minute. Range = 0.5 - 8.5 minutes in 30 second
increments.
LED Brightness - Default = 100. Range is 0 - 255.
Darkness Sensitivity - The higher the value, the darker it needs to be for the unit
to see night. Default = 35. Range = 0 - 255.
RemoteLinc
RemoteLincs are RF devices, thus require the installation of an INSTEON RF receiver
(such as an INSTEON AccessPoint).
RemoteLincs link differently than other INSTEON devices, this require a separate
linking routine. To link a RemoteLinc to your ISY, click the LINK MANAGEMENT
pulldown and choose LINK A REMOTELINC and follow the on-screen instructions.
Since the RemoteLinc is a battery-saving RF device, it must be put into linking mode
whenever adding to the ISY or making changes (such as adding or removing from a
scene). To put the device in linking mode, hold Button 1 down for 10 seconds, or until